• Samurai Full Protect

Specifications

     

  • Samurai Full Protect is our solution for small and medium-size data centers
  • Samurai Full Protect range includes several solutions for different data centers power requirements
  • From the small Samurai Full Protect in a sole cabinet, that is like a small data center room, to the modular Samurai
  • Full protect that is designed to satisfy the most powerful computers
  • Is an air-conditioned cabinet: inside is located the server (and its accessories as hubs, switch boards, etc.), and the redundant modular uninterruptible power systems (UPS) with their sealed batteries. The air conditioner automatically optimizes both the temperature inside the cabinet and the energy consumption

Application

Samurai Full Protect
Samurai Full Protect

Technical specification

Samurai Power Water System Model SFP162 SFP162E1 SFP222E1 SFP323E1
Total cooling capacity 16 32
Number of fans (N˚) 3
Airflow max (automatic variations of speed) (m3/h) 2600 4000
Water flow (l/h) 3700 5070 6200
UPS* (N + 1)
N˚ modules (N˚) 1+1 2+1 3+1
Power module (kW) 12
N˚ max batteries 9Ah / 12V (N˚) 120 200
Backup time (N˚ UPS load) 40 min 25 min 15 min
Input voltage (V/ph/Hz) 400 / 3 + N / 50
Output voltage (V/ph/Hz) 400 / 3 + N / 50
Cabinet physical data
Weight (kg) 720 1180 1125 1310
Dimensions W x D x H (mm) 950 x 1200 x 2100 950 x 1550 x 2100
Server rack unit available (U) (45,45mm) 17 42
External chiller unit
Input voltage (V/ph/Hz) 400 / 3 + N / 50
Cooling capacity (kW) 16 22 32
Samurai Power Gas System Model SFP081 SFP081E1 SFP202E1
Total cooling capacity 8 20
Number of fans (N˚) 3 5
Airflow max (automatic variations of speed) (m3/h) 2600 40000
Gas refrigerant R410 A
UPS* (N + 1)
N˚ modules (N˚) 1+1 2+1
Power module (kW) 12
N˚ max batteries 9Ah / 12V (N˚) 120 200
Backup time (N˚ UPS load) 40 min 25 min
Input voltage (V/ph/Hz) 400 / 3 + N / 50
Output voltage (V/ph/Hz) 400 / 3 + N / 50
Cabinet physical data
Weight (kg) 720 980 1125
Dimensions W x D x H (mm) 950 x 1200 x 2100 950 x 1550 x 2100 950 x 1550 x 2100
Server rack unit available (U) (45,45mm) 17 42
External motor condensing unit
Input voltage (V/ph/Hz) 400 / 3 + N / 50
Cooling capacity (kW) 8 20

We are always ready to help you!