• Samurai TC 10–40 kVA

Specifications

  • On-line “double conversion” technology (VFI)
  • Parallel redundancy On-line UPS (up to 4 units)
  • Input power factor up to 0.99 (PFC technology)
  • DSP (Digital Signal Processor) technology
  • Common battery string for parallel units
  • IGBT technology (rectifier and inverter)
  • Internal static and manual bypass
  • 16/18/20/40 pcs 12V batteries per string (adjustable)
  • 32/36/40 pcs 12 V batteries per string for 40 kVA units (adjustable)
  • ECO-mode for energy-saving
  • Intelligent charging management
  • Self-test during UPS start-up
  • Internal and external batteries
  • Unbalanced load acceptable (generator mode)
  • Wide input voltage range
  • Battery (DC) cold start
  • LCD-LED double display with audible/visible alarms
  • ES485 and USB ports, dry contacts
  • EPO (Emergency Power Off)
  • Backfeed protection

Application

Samurai TC 10–40 kVA
Samurai TC 10–40 kVA
Samurai TC 10–40 kVA
Samurai TC 10–40 kVA

Price-performance Ratio

The TC series is our best “price-performance ratio” 3/3 phase UPS. Based on our modular UPS technology, we are able to offer extremely small UPS 10-30kVA solutions. A combination of our modular based UPS with a special DC/DC converter, the TC UPS can work with a battery voltage of only 192 to 240 V DC (adjustable). It allows to reduce space, batteries and price.

Technical specification

Samurai Power
TC 3/3
10000 15000 20000 30000 40000
Power (VA / Watt) 10 kVA / 9 kW 10 kVA / 13,5 kW 20 kVA / 18 kW 30 kVA / 27 kW 40 kVA / 36 kW
Input
Nominal voltage 380 / 400 / 415 V AC (3 ph+N+PE)
Maximum voltage 208 ~ 478 V AC
Frequency range 43 ~ 65 Hz
Power factor 0.99
Harmonic distortion (THDi) < 3% (at 100% non-linear load)
Bypass voltage range -45%, +15%
Bypass frequency range +/- 10%
Output
Voltage regulation 380 / 400 / 415 V +/- 1% at nominal load
Frequency 50 / 60 Hz +/- 0,1 Hz at nominal load
Efficiency at 75 – 100% load 94% On-line mode / 97% ECO mode
Harmonic distortion (THD) < 2% linear load, < 5% non-linear load
Bypass Internal static (automatic) and manual bypass / External bypass optional
Transfer time Mains to battery: 0 ms, mains to bypass: 0 ms
Crest factor 3:1
Battery
Voltage (adjustable) 192 / 216 / 240 / 480 V DC 384 / 432 / 480 V DC
Charging current Depends on battery configuration
Protection
Input/output Overvoltage, short-circuit, battery deep discharge, thermal protection
Overload AC/battery ≤ 110%: 60 min, ≤ 125%: 10 min, ≤ 150%: 1 min, > 150: switch to bypass mode
Alarms – informations
Audible alarm Line failure, battery low, bypass-overload status, fault status
LED Line- / backup- / ECO- / bypass-mode, battery low / bad / disconnected, overload, fault
LCD Voltage / frequency, load %, battery voltage/runtime
Standard
Safety IEC / EN62040-1, IEC/EN60950-1
EMC IEC / EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC6100-4-4, IEC6100-4-5, IEC61000-4-8
Protection class IP20
Dimensions
Weight – without batteries (kg) 42 42 45 45 67
W x D x H (mm) 250 x 828 x 868
Environment
Temperature / Humidity 0 ~ 40 ˚C / 0 ~ 95% (non-condensing)
Audible noise at 1m < 55 dB < 58 dB
Interface
Standard RS232, USB, EPO, intelligent slot
Optional SNMP, relay card