Specifications
Options
Application


Optimize your investments
Power consumption and power requirements are constantly changing. With our VFI Modular you can simply increase or decrease the UPS power according to your needs. This is fast and cost effective when you increase the UPS by small steps. During a period of less requirements/power consumption, you simply remove UPS modules to save energy costs.
Technical specification
Samurai VFI Modular |
60 kVA 3/3 | 100 kVA 3/3 | 210 kVA 3/3 | 310 kVA 3/3 | |
---|---|---|---|---|---|
Capacity | 10 ~ 30 kVA / 9 ~ 27 kW 20~60 kVA / 18 ~ 54 kW |
20 ~ 100 kVA / 18 ~ 90 kW |
20 ~ 200 kVA / 18 ~ 180 kW |
30 ~ 300 kVA / 27 ~ 70 kW |
|
Power per module | 110 kVA / 9 kW 20 kVA / 18 kW |
20 kVA / 18 kW | 30 kVA / 27 kW | ||
Input | |||||
Terminals | L1, L2, L3, N, PE | ||||
Rated voltage | 380 / 400 / 415 V AC | ||||
Voltage range | 208 ~ 478 V AC | ||||
Power factor | ≥ 0.99 | ||||
THDi | < 3% (100% / non linear load) | ||||
Maximum voltage range bypass | +15% (optional + 5%, + 10%, + 25%) | ||||
Minimum voltage range bypass | -45% (optional – 20 %, – 30%) | ||||
Frequency protection range | ±10% | ||||
Generator input | Supported | ||||
Output | |||||
Rated voltage | 380 / 400 / 415 V AC | ||||
Power factor | 0.9 | ||||
Voltage regulation | ± 2% | ||||
Frequency | Utility mode | ±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency (optional) | |||
Battery mode | 50 / 60 Hz ± 0.2% | ||||
Crest factor | 3:1 | ||||
THD | ≤ 2% (linear load); ≤ 5% (non-linear load) | ||||
Waveform | Pure sinewave | ||||
Efficiency | ECO mode > 98% / Normal mode up to 95% | ||||
Battery | |||||
Voltage | 192, 201, 216, 228, 240 V DC; depending on the battery set | ||||
Charging current (max) | 18 A | 30 A | 60 A | 100 A | |
Protection | |||||
Overload capability (utility mode) | ≤ 110% for 60 min; ≤ 125% for 10 min; ≤ 150% for 1 min; ≤ 150% for 1 min switch to bypass | ||||
Overload capability (battery mode) | ≤ 110% for 10 min; ≤ 125% for 1 min; ≤ 150% for 15 s; ≤ 150% shut down UPS immediately | ||||
Overload capability (bypass mode) | Module breaker: 10 kVA at 20 A, 20 kVA at 40 A, 30 kVA at 63 A | ||||
Short circuit | Hold whole system | ||||
Self-diagnostics | Upon power on and software control | ||||
EPO | Shut down UPS immediately | ||||
Battery | Advanced battery management | ||||
Regulations/Standards | |||||
Safety | EN 62040-1 | ||||
EMC | EN 62040-2 Class C3 | ||||
Certifications | CE |