VFI Modular 200kVA 3/3
Features
Suitability
MODEL | VFI-200 kVA 3/3 |
---|---|
Capacity | 20–200kVA/18–180kW |
Power module | 20kVA/18kW |
INPUT | |
Terminals | L1, L2, L3, N, PE |
Rated voltage | 380/400/415 VAC |
Voltage range | 208~478 VAC |
Frequency range | 40 Hz–70 Hz |
Power factor | ≥ 0.99 |
THDi | < 3% (100%/non-linear load) |
Voltage range bypass | Max voltage: +15% (optional +5%, +10%, +25%) Min. voltage: –45% (optional –20%, –30%) Frequency protection range: ±10% |
Generator input | supported |
OUTPUT | |
Terminals | L1, L2, L3, N, PE |
Rated voltage | 380/400/415 VAC |
Power factor | 0.9 |
Voltage regulation | ±2% |
Frequency – Utility mode | ±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency (optional) |
Frequency – Battery mode | 50/60 Hz ± 0,2% |
Crest factor | 3:1 |
THD | ≤ 2% (linear load); ≤ 5% (non-linear load) |
Waveform | Pure sinewave |
EFFICIENCY | 95% |
BATTERY | |
Voltage | 192, 204, 216, 228, 240 VDC; depending on the battery set |
Charging current | Max 60A |
PROTECTION | |
Overload – Utility mode | ≤ 110% for 60 min; ≤ 125% for 10 min; ≤ 150% for 1 min, ≤ 150% switch to bypass |
Overload – Battery mode | ≤ 110% for 10 min; ≤ 125% for 1 min; ≤ 150% for 15 s, ≤ 150% shut down UPS immediately |
Overload – Bypass mode | Module breaker: 10kVA @ 20A, 20kVA @ 40A, 30kVA @ 63A |
Short circuit | Hold whole system |
Self-diagnostics | Upon power on and sofware control |
EPO | Shut down UPS immediately |
Battery | Advanced battery management |
REGULATIONS/STANDARDS | |
Safety | EN 62040-1 |
EMC | EN 62040-2 Class C3 |
Certifications | CE |
VFI Modular 60 kVA 3/3 can support up to 3 modules, the 100 kVA up to 5 and the VFI Modular 200 kVA or 300 kVA 3/3 can accommodate up to 10 modules.
Up to 4 module containing units can be installed in parallel.